The Private Water Supplies Regulations 2009

PART 2Indicator Parameters

TABLE C

Prescribed concentrations, values or states

ParametersMaximum concentration or value or state (unless otherwise stated)Units of measurement
(i)

The water should not be aggressive.

(ii)

Excluding tritium, potassium-40, radon and radon decay products.

(iii)

Only in the case of surface water or groundwater that has been influenced by surface water.

Ammonium0.50mg/l
Chloride (i)250mg/l

Clostridium perfringens

(including spores)

0

Number/100ml

Coliform bacteria0Number/100ml (Number/250 ml in the case of water put into bottles or containers)
Colony counts

No abnormal change

No abnormal change

Number/ml at 22°C

Number/ml at 37°C

Conductivity (i)2500μS/cm at 20°C
Hydrogen ion9.5 (maximum)pH value

6.5 (minimum) (in the case of still water put into bottles or containers the minimum is 4.5)

pH value
Sulphate (i)250mg/l

Total indicative dose (for radioactivity) (ii)

0.10mSv/year
Total organic carbon (TOC)No abnormal changemgC/l

Tritium

(for radioactivity)

100Bq/l
Turbidity(iii)1NTU